OXeN heating and ventilation unit with heat recovery is an innovative device on the market that allows fresh air to enter a room and recover the heat energy already generated. Due to its functionality and design, the OXeN unit has received many design awards.
OXeN is the only such device available on the market that provides mechanical supply and exhaust ventilation without the need for ductwork. OXeN is an easy-to-install, energy-efficient ductless ventilation system. It can significantly reduce investment costs and its high heat recovery efficiency reduces operating costs.
The application of OXeN units on the site ensures adequate circulation and a positive effect on the quality of the indoor air, while saving money through heat recovery. In addition, using the intelligent FLOWAIR SYSTEM control, the device knows exactly when to work. The T-box controller with touchscreen display, which is the brain of the SYSTEM, also controls all devices from one place.
Basic parameters
Air flow | 1200 m3/h |
---|---|
Heat recovery efficiency | do 80,9% |
Heat recovery capacity | do 6,0 kW |
Mass | 75,1 - 82,4 kg |
Casing | expanded polypropylene EPP |
Provides low investment and operating costs, is easy to maintain, perfect for existing buildings.
Each unit is equipped with a complete automation system for intuitive and reliable operation of the unit.
OXeN heat recovery unit is a unit that is immediately ready for operation. No additional mounting consoles are required, as it comes with mounting brackets as standard.
The device is made of extremely durable yet lightweight material. Expanded polypropylene (EPP) provides good thermal insulation and high noise dampening capacity.
Application
OXeN unit is designed for indoor operation providing energy-efficient ventilation to medium and large volume buildings such as petrol stations, shops, workshops, warehouses or sports halls.
Device advantages
X2-FLOW - high heat recovery efficiency was achieved by using two cross-flow heat exchangers. The exchangers are made of aluminium, so they provide high corrosion resistance.
MULTI-FAN TECHNOLOGY - the unit uses two diagonal fan sections, each consisting of 3 units. This allows for even distribution of the supply air flow over the entire surface of the exchanger, efficient heat exchange, quiet operation and energy efficiency.
EPP CASING - the unit's housing is made from
an extremely strong yet lightweight material. Expanded polypropylene (EPP) provides good thermal insulation, high noise dampening capacity and has significantly reduced the overall weight of the unit.
Device types available
- X2-W-1.2-V - wall-mounted unit with water heater,
- X2-E-1.2-V - wall-mounted unit with electric heater,
- X2-N-1.2-V - wall-mounted unit without supplementary air heater,
- X2-W-1.2-H - ceiling-mounted unit with water heater,
- X2-N-1.2-H - ceiling-mounted unit without supplementary air heater..
A solution worthy of awards
The OXeN ventilation unit has received several instrutrial design awards. The most prestigious awards the unit has won are the RedDot 2014 title and IF Design. These awards are not only an affirmation of the device's reliability, but also of the appropriate design adapted to functionality.
X2-W-1.2-V | X2-N-1.2-V | X2-W-1.2-H | X2-N-1.2-H | X2-E-1.2-V | |
---|---|---|---|---|---|
Max. air flow stream inlet/outlet [m3/h] | 1200* | 1200* | 1200* | 1200* | 1200* |
Air stream range [m] | Poziomy, 15** | Poziomy, 15** | Pionowy, 4,5*** | Pionowy, 4,5*** | Poziomy, 15 |
Air flow regulation inlet/outlet [m3/h] | stepless 150–1200 | stepless 150–1200 | stepless 150–1200 | stepless 150–1200 | none |
Acoustic pressure level [dB(A)] | 49**** | 49**** | 49**** | 49**** | 49**** |
Power supply [VAC/Hz] | 230/50 | 230/51 | 230/52 | 230/53 | 3x400 |
Max. current consumption [A] | 1,9 | 1,9 | 1,9 | 1,9 | 14 |
Max. power consumption [kW] | 0,42 | 0,42 | 0,42 | 0,42 | 8,5 |
Type of casing | expanded polypropylene EPP | expanded polypropylene EPP | expanded polypropylene EPP | expanded polypropylene EPP | expanded polypropylene EPP |
Color | grey***** | grey***** | grey***** | grey***** | grey***** |
Mass | 77,5 | 75,1 | 80,5 | 78,1 | 82,5 |
Weight of unit filled with water [kg] | 78,3 | – | 81,3 | – | – |
Place of installation | inside the buildings | inside the buildings | inside the buildings | inside the buildings | inside the buildings |
Max. air contamination [g/m3] | 0,3 | 0,3 | 0,3 | 0,3 | 0,3 |
Oparating temperature [°C] | 5–35 | 5–35 | 5–35 | 5–35 | 5–35 |
Installation position | vertically on the wall | vertically on the wall | under the ceiling | under the ceiling | vertically on the wall |
IP | 42 | 42 | 42 | 42 | 42 |
Filter class | EU4 | EU4 | EU4 | EU4 | EU4 |
Type of heat recovery exchanger | two-step heat recovery in cross heat exchangers | two-step heat recovery in cross heat exchangers | two-step heat recovery in cross heat exchangers | two-step heat recovery in cross heat exchangers | two-step heat recovery in cross heat exchangers |
Thermal efficiency dry / wet [%] | 74,7/ 80,9****** | 74,7/ 80,9****** | 74,7/ 80,9****** | 74,7/ 80,9****** | 74,7/ 80,9****** |
Type of additional heater | water heater | – | water heater | – | water heater |
Nominal heating capacity [kW] | 10******* | – | 10******* | – | 8,5 |
Air temperature rise (ΔT) [°C] | 25******* | – | 25******* | – | – |
Connection [”] | 1/2 | – | 1/2 | – | – |
Max. water pressure [MPa] | 1,6 | – | 1,6 | – | – |
Max. water temperature [°C] | 95 | – | 95 | – | – |
Control system | controller with touch screen | controller with touch screen | controller with touch screen | controller with touch screen | controller with touch screen |
Antifreeze protection of heat recovery exchanger | reduction of fan revs | reduction of fan revs | reduction of fan revs | reduction of fan revs | reduction of fan revs |
** Range of isothermal air stream, at 0,2 m/s velocity limit.
*** Range of horizontal isothermal air stream, Range of vertical nonisothermal air stream, (Δt=5°C) 0.2 m/s velocity limit
**** Acoustic pressure level at the distance of 5 m from the unit, in the room of medium capability of sound absorption and 500 m3 of cubature.
***** Similar to RAL 9007
******According to directive 2009/125/EC measured with balanced mass flow, an indoor-outdoor air temperature difference of 20 K and the airflow 1200m3/h
******* At water temperature 80/60oC, inlet air temperature 5oC and 1200 m3/h of air flow
Ceiling and wall mounting
The unit comes with mounting brackets as standard, so no additional frames or brackets are required.
Download files