| Evoluzione heaters have been designed for elegant medium- and large-size interiors: gyms, fitness centers, supermarkets, commercial interiors, churches, exhibition showrooms, car showrooms, etc. |
| Evoluzione heaters are devices that are characterized by a modern, elegant design. There are three models available with double control of burner power from 19.35 kW up to 44.5 kW. |
| A double-stage burner cooperates with a double-stage blowing fan ensuring a limited noise level - 36 dB(A) (nominal value of the E32 model in open air). |
| A stainless steel combustion chamber ensures safety and long, failure-free operation; it is connected through clamping with aluminium exchangers. |
| The floor effect, which is created due to the special construction of the heat exchanger (different temperature and air speed in various places of the exchanger), allows the significant reduction of energy consumption and effectively keeps warm air in an area of human presence. |
| The fan burner ensures high efficiency and extremely low NOx emission of combustion gases – reducing environmental impact. |
|
Nominal heat input
|
|
kW |
26,00 |
37,15 |
48,35 |
|
Nominal heat output
|
nominal |
kW |
24,20 |
34,20 |
44,50 |
| reduced |
kW |
19,35 |
27,40 |
35,60 |
|
Efficiency
|
|
% |
93 |
92 |
92 |
|
Nominal gas consumption (1)
|
natural gas |
m3/h |
2,75 |
3,93 |
5,11 |
| LPG G30 |
kg/h |
2,05 |
2,93 |
3,81 |
| LPG G31 |
kg/h |
2,01 |
2,90 |
3,74 |
|
Reduced gas consumption (1)
|
natural gas |
m3/h |
2,20 |
3,15 |
4,09 |
| LPG G30 |
kg/h |
1,64 |
2,34 |
3,05 |
| LPG G31 |
kg/h |
1,61 |
2,30 |
2,99 |
|
Nominal air flow (2)
|
at maximum speed |
m3/h |
2300 |
3400 |
4200 |
| at minimum speed |
m3/h |
1900 |
2700 |
3400 |
|
Temperature rise
|
at maximum speed |
K |
31,2 |
29,4 |
31,0 |
| at minimum speed |
K |
30,2 |
29,8 |
30,7 |
|
Gas connection
|
|
" |
3/4 |
|
Air inlet pipe diameter
|
|
mm |
80 |
|
Exhaust air pipe diameter
|
|
mm |
80 |
|
Electrical voltage
|
|
|
230V/50Hz |
|
Installed wattage
|
|
W |
250 |
350 |
420 |
|
Air throw at maximum speed (3)
|
|
m |
14 |
20 |
22 |
|
Recommended installation height
|
|
m |
2,5/3 |
2,5/3 |
3/3,5 |
|
Operating temperature range (4)
|
|
oC |
0/35 |
|
Sound pressure level at
maximum speed at 6 metres
|
in open field |
dB(A) |
38 |
40 |
42 |
| in typical installation |
dB(A) |
48 |
52 |
56 |
|
Sound pressure level
at 6 metres
|
in open field |
dB(A) |
36 |
37 |
38 |
| in typical installation |
dB(A) |
45 |
47 |
51 |
|
Weight
|
|
kg |
60 |
66 |
74 |
(1) At. 15
oC - 1013 mbar.
(2) At. 20
oC - 1013 mbar.
(3) Throw for guidance only. Throw depends on height of building, mounting height
to heater, room temperature and louvre setting.
(4) Indoor temperature of the installation location. The unit’s internal components
have been tested from 0 °C to 60 °C.