| F series heaters are meant for heating various facilities: warehouses, supermarkets, industrial buildings and workshops. |
| Gas heaters are meant for internal installations. We offer 7 models of heating power from 21 up to 92 kW. |
| The device in the version equipped with an axial fan ensures high efficiency. The burner, made of stainless steel, achieves efficiency of 92% and reduces NOx emission. |
| The stainless steel combustion chamber ensures safety and long, failure-free operation; it is connected through clamping with aluminium exchangers. |
| The floor effect, which is created due to the special construction of the heat exchanger (different temperature and air speed in various places of the exchanger), allows significant reduction of energy consumption and effectively keeps warm air in an area of human presence. |
| There are various chimney systems proposed for the heaters – running through the wall, roof, coaxial and separable. There are also various endings for facades with protective caps. |
|
Nominal heat input
|
|
kW |
23,08 |
30,77 |
37,15 |
48,35 |
60,00 |
80,00 |
100,00 |
|
Nominal heat output
|
|
kW |
21,00 |
28,00 |
33,80 |
44,00 |
55,20 |
73,60 |
92,00 |
|
Efficiency
|
|
% |
91 |
91 |
91 |
91 |
92 |
92 |
92 |
|
Nominal gas consumption (1)
|
natural gas |
m3/h |
2,43 |
3,25 |
3,93 |
5,11 |
6,35 |
8,47 |
10,58 |
| LPG G30 |
kg/h |
1,80 |
2,42 |
2,93 |
3,81 |
4,73 |
6,31 |
7,88 |
| LPG G31 |
kg/h |
1,78 |
2,38 |
2,87 |
3,74 |
4,66 |
6,22 |
7,77 |
|
Nominal air flow (2)
|
|
m3/h |
2000 |
2700 |
3400 |
4200 |
5350 |
6300 |
8250 |
|
Temperature rise
|
|
K |
31,1 |
30,7 |
29,5 |
31,0 |
30,6 |
34,6 |
33,0 |
|
Gas connection
|
|
" |
3/4 |
|
Air inlet pipe diameter
|
|
mm |
80 |
|
Exhaust air pipe diameter
|
|
mm |
80 |
|
Electrical voltage
|
|
|
230V/50Hz |
|
Installed wattage
|
|
W |
260 |
400 |
400 |
450 |
750 |
650 |
900 |
|
Air throw (3)
|
|
m |
14 |
16 |
20 |
22 |
31 |
36 |
40 |
|
Recommended installation height
|
|
m |
2,5/3 |
2,5/3 |
2,5/3 |
3/3,5 |
3/3,5 |
3/3,5 |
3/4 |
|
Operating temperature range (4)
|
|
oC |
0/35 |
|
Sound pressure level
at 6 metres
|
in open field |
dB(A) |
41 |
43 |
44 |
46 |
50 |
52 |
54 |
| in typical installation |
dB(A) |
53 |
55 |
56 |
57 |
61,5 |
63 |
65,5 |
|
Weight
|
|
kg |
55 |
59 |
68 |
80 |
75 |
98 |
120 |
(1) At. 15
oC - 1013 mbar.
(2) At. 20
oC - 1013 mbar.
(3) Throw for guidance only. Throw depends on height of building, mounting height
to heater, room temperature and louvre setting.
(4) Indoor temperature of the installation location. The unit’s internal components
have been tested from 0 °C to 60 °C.