| These gas heaters are meant for internal installations.: the ideal application in warehouses, production plants, supermarkets, and interiors needing continuous ventilation.
The equipment can be used with air ducts and fresh-air ventilation pipes. |
| We also Offer:
-Air mixing units equiped with two independent air dampers, elastic connections and filters
- control systems, automatics (standart or individual solution)
-lifting sling which makes it possible to mount the unit on a partition
-chimney exhaust systems |
| |
Nominal heat input
|
|
kW |
20,6 |
34,8 |
72,5 |
Nominal heat output
|
|
kW |
18,3 |
30,7 |
63,8 |
Efficiency
|
|
% |
88,8 |
88,2 |
88,0 |
Gas consumption (1)
|
natural gas |
m3/h |
2,18 |
3,68 |
7,67 |
| LPG G30 |
kg/h |
1,62 |
2,74 |
5,72 |
| LPG G31 |
kg/h |
1,59 |
2,69 |
5,61 |
Air flow (2)
|
with free outlet |
m3/h |
2900 |
4300 |
7600 |
| at maximum admissible pressure drop |
m3/h |
1600 |
3100 |
5800 |
Temperature rise
|
with free outlet |
K |
19 |
21 |
24,5 |
| at maximum admissible pressure drop |
K |
32 |
32 |
31 |
Available pressare head
|
|
Pa |
110 |
Gas connection
|
|
" |
1/2 |
1/2 |
3/4 |
Air inlet pipe diameter (3)
|
|
mm |
130 |
Exhaust air pipe diameter (3)
|
|
mm |
110 |
Electrical supply
|
|
|
230V/50Hz |
Installed wattage
|
|
W |
600 |
620 |
920 |
Operating temperature range (4)
|
|
oC |
0/35 |
Weight
|
|
kg |
66 |
82 |
133 |
(1) At. 15
oC - 1013 mbar.
(2) At. 20
oC - 1013 mbar.
(3) Nominal diameter of rigid pipe to be inserted into specific cylindrical housing.
(4) Indoor temperature of the installation location. The unit’s internal components have
been tested from 0 °C to 60 °C.